General Specification:

  • Conventional fire alarm and fire extinguishing panel, based on Bus technology. Flexibility and economy in installation.
  • Outputs expandability: 8 to 72 relays, 1 per zone.
  • Cross-zoning/fire extinguishing feature: Up to 18 fire extinguishing areas. Fire extinguishing set up by using 4 zones and 4 relays. A reliable alarm status detection and then a sequence of relay activations transform the system in a gas fire-extinguishing system. Any four zones with corresponding relays can be programmed as a fire extinguishing area.
  • LCD keypad for system supervision, monitoring, operations and programming: Up to 8 display devices/keypads.
  • Two general alarm siren relay outputs. Activated when the system enters an alarm status. The first output generates continuous siren activation. The second one generates a different pattern (e.g. ANSI evacuation pattern).
  • One (1) main general fault output (not monitored): Dry contact relay 3A max. Gets activated when any fault condition is detected.
  • One (1) general fault relay: Dry contact relay 3A max. Activated when some kind of fault is detected.
  • Encoder: Communication with the Central Signal Receiving Station via PSTN telephone line, using a Contact ID format.
  • Bypass (zones disarm/isolation) feature, regardless zone inputs and relay outputs. Intellizone feature: Verification of the actual cause of an alarm before the system enters an alarm status.
  • Day/Night Mode: Reducing false alarms at certain time intervals of the day through Intellizone feature. As an example, zones in smoking areas during working hours are automatically adjusted to Intellizone while acting as direct zones during the remaining time. Programmable Day/Night time.
  • 3 options for full building evacuation: Manual fire call points or/and a keypad combination or/and fire extinguishing zones can be used to activate full evacuation.
  • Walk test: The user may activate a test status on the panel. During the test, he manually triggers each detector and the sirens are activated for a short time period.
  • Events recording (Logging): Storage of up to 1,000 events.
  • Local or Remote system supervision, monitoring, operations and programming via network or RS-232 and special software Fighter ProVision and FRS-232 module.
  • Certified according the European Union Directives EN 54-2:1997/A1: 2006/AC: 1999, EN 54-4:1997/A2: 2006/AC: 1999 & EN 12094-1:2003 (Fire extinguish). Certification No 123-CPD-0308 of July 2, 2012.